Adapter module ADP-N3E

784744

Microprocessor-controlled module for installation (mounting rail) in System 8000 or IQ8Control fire alarm panels. In compliance with DIN 14675, the TTY interface can be used for redundant transmission when the adaptor is connected and when the fire brigade indicating panel FAT 3000 is used for initially informing the fire brigade. Additional text ( 4,000 texts) can be programmed using a PC with serial interface connection.
  • Input: TTY from the internal FACP interface
  • Output: DUAL RS 485 to the FAT interface


Additional Information:

The top hat rail module (Part No. 788652) and the module housing for snap-on mounting rail (Part No. 788603.10) can be used for installation. The interface is compatible with FAT 3000 (Part No. 784743). Power is supplied by the fire alarm panel or an external power supply unit. Maximum data line length: 800 m.
Connection terminalmax 2 x 0.8 mm²
Operating voltage8 ... 30 V DC
Weight gapprox. 100 g
Contact load relay30 V DC / 1 A
Storage temperature-10 °C ... 60 °C
Quiescent current @ 12 V DCapprox. 55 mA
Ambient temperature-5 °C ... 40 °C
DimensionsW: 80 mm H: 150 mm D: 30 mm