Addressable wall mounted isolated sounder, red

WSO-PR-I05

Honeywell Morley-IAS wall mounted sounder is installed in exactly the same manner as an intelligent fire detector. Common installation base (Part No. MI/B501AP/IV), which accepts any product within Honeywell Morley-IAS audiable-visual product family, is installed at first fix. This common base is fitted with a shorting spring, enabling loop continuity to be maintained without having to install any Honeywell Morley-IAS audiable-visual product. It also removes the need to separately test wiring. As the sounder itselfs does not have to be installed until final commissiong, there is no risk of damage during first fix. By utilising the latest developments in piezoelectric transducer the sounder is highly efficient. Current consumption is minimised, enabling the maximum number of devices to be installed on a loop, without compromising on Sound levels.
  • 32 built-in tones
  • Rotary decade adress switches
  • Lower power requirements
  • Optional IP65 rating
  • Optional built-in isolator
  • Anti-Tamper feature
  • Specifications: EN54-3, EN54-17
  • LPCB approved
Operating voltage15 ... 32 V DC (without isolator) 15 ... 28 V DC (with isolator)
Dimensionø: 121 mm H: 64 mm
Weight238 g
Colorred
Ingress protectionIP24 (with low profile base) IP44 (with surface mount base) IP65 (waterproof base)
Max. wire guage1.5 ... 2.5 mm2 max
Quiescent current120 uA (non-isolation) 225 uA (isolation)
Alarm current11.4 mA (high volume tone 21 @ 24 V)
Relative humidity< 95 % (non-condensing)
Max sound output97dB(A) +/-3dB @ 1 m
Temperature range -25°C ... +70°C
  • MI/B501AP/IV Detector and AV standard base
  • BRR Deep profile base red with MI/B501AP/IV
  • WRR Deep waterproof base, red