DXc1, Single-loop control panel, latin letters

714/001/117

DXc1 is a single-loop fire control panel. It can operate as stand-alone or networked system with other DXc series panels up to 16 loops.
  • Networking up to 16 loops
  • 1 loop control panel (inbuilt loop card)
  • 6x40 characters, blue liquid crystal display with backlight illumination
  • Supports Austrian, Turkish, Polish, Romanian, Hungarian, Czech, Slovakian, Slovenian, Croatian, Lativa, Lithuania and Estonia languages
  • Option to upload compay logo
  • Configuration by Keypad and PC
  • 160 Fire Zones
  • RS-485 port for peripherals connection
  • 2 programmable output sounder circuits (monitored)
  • Fire, Fault and Auxiliary relay (each one)
  • Loop-Battery calculator for reliable system design
  • 7 day timer
  • Onboard diagnostic
  • Specification EN54-2, EN54-4
  • LPCB approved
Operating voltage 230 V, 50-60 Hz AC (+15%,-15% tolerance)
Max PSU rating 2 A / 24 V DC
Auxiliary output 24 V DC / 250 mA
Loop load 500 mA
Ambient temperature 0°C ... 40°C
Humidity 5% ... 95% non-condensing
Batteries 2 x 12 V / 7 Ah
Dimension H: 260 mm W: 390 mm D: 147 mm
Weight 4 kg
Color gray white, similar to RAL 9002
Ingress protection IP30
Cable entry 25 x 20 mm knock-outs at the top and 2 x 20 mm knock-outs at the bottom
Sounder ckt Rating 1 A
Housing material Mild Steel (rear enclosure), ABS plastic front cover complying BS EN60950