Optical alarm signaling device, EN 54-23 cat. W+C, white flash, red housing

CWST-RW-S5

Optical signaling device compliant with EN 54-23 for wall and ceiling mounting with white lamp color and flat base. The signaling device is suitable for square signal ranges W-2.4-6.2 and cylindrical signal ranges C-3-9.4 / C-6-8.2.
To help define your conventional Visual Alarm Devices (VADs) requirements in line with the EN54-23 standard, we have developed an easy to use online guide. Simply enter the room dimensions and ambient light conditions and the guide will help your device selection: http://www.kac.co.uk/EN54-device-chooser.htm

  • EN 54-23 compliant
  • C & W category
  • Synchronous flash trigger
  • Up to 6.2 m room width for wall mounting
  • Up to 9.4 m room diameter for ceiling mounting

Additional Information:

Not suitable for use outdoors or in damp areas. Please use therefore the optional bases and accessories (Part No. CWR, PS188, PS189). Replacement for Part No. 766420, 766422, 766410.
Connection terminal 0.5 ... 2.5 mm²
Operating voltage 12 ... 29 V DC
Flash color white
Frequency of flash approx. 0.5 Hz
Color base: red, similar to RAL 3020 / cap: transparent
Weight
approx. 164 g
Category ceiling C-3-9,4 / C-6-8,2
Category wall W-2,4-6,2
Material PC/ABS (Body); PC (Lens)
Mounting height ceiling 3 m / 6 m
Mounting height wall 2.4 m
Space width 6.2 m
Room diameter 9,4 m / 8,2 m
Air humidity < 96 % (non-condensing)
Type of protection IP 21C, IP 65 with base CWR
Specification EN 54-23 optical signaling device
Current consumption @ 24 V DC approx. 37 mA
Ambient temperature -25 °C ... 70 °C
Dimensions ø: 100 mm H: 72 mm
ø: 100 mm H: 97 mm (incl. IP base)

  • CWR Base deep IP 65, red
  • PS188 Base deep, O-Ring
  • PS189 Base deep, seal