Fire brigade indicating panel FAT 3000-EDP protocol, Czech

FX808380.CZ

Approval: VdS

Microprocessor-based fire brigade indicating panel according to DIN 14675 as an additional alarm device for a FlexES fire detection panel. Serial connection to the fire alarm panel via the RS 485 interface. In addition, a serial fire brigade indicating panel can be connected via an RS 232. Conventional as well as redundant operation is possible via ADP-N3E adapters according to DIN 14675. The collective indicators and operating keys enable the fire brigade to receive a comprehensive overview of the on-site situation. Up to 4,000 PC-programmable supplementary texts, event memory and the possibility of a short-circuit and interruption-tolerant loop installation guarantee superior safety levels. The ESPA interface facilitates a direct connection which is not galvanically separated to a telecommunication system or paging system. Compliant with DIN 14662: Z-2012.

Alarm current @ 24 V DCapprox. 60 mA
Operating voltage10 ... 30 V DC
Colorgray, similar to RAL 7032
Housingsheet steel
Weight kg approx. 3.5 kg
Quiescent currentapprox. 40 mA
Quiescent current @ 24 V DCapprox. 40 mA
Type of protectionIP 30
VdS-NrG 205076
DimensionsW: 255 mm H: 185 mm D: 58 mm