Adapter module ADP-N3EU-EDP

FX808381

Microprocessor-based device for installation in FlexES fire alarm panel. In compliance with DIN 14675, the TTY interface of the fire alarm panel can be used as a redundant data bus with this adapter if the fire brigade indicating panel FAT 3000 is used for the fire brigade’s initial information. Supplementary texts can be programmed via PC (> 4,000 texts).

The ESPA interface facilitates a direct connection which is not galvanically isolated to a telecommunication system, paging system or nurse call system.
  • Input: EDP protocol
  • Output: ESPA protocol
Connection terminal max 2 x 0.8 mm²
Operating voltage 10 ... 30 V DC
Weight approx. 100 g
Contact load relay 30 V DC/ 1 A
Storage temperature -10 °C ... 60 °C
Quiescent current approx. 40 mA
Ambient temperature 0 °C ... 50 °C
Dimensions W: 80 mm H: 150 mm D: 32 mm