Explosion-proof conv. MCP, IP66

761697.1

The manual call point was developed for explosion hazard areas, where gas or dust can cause an explosive atmosphere. The device provides a maximum security, without using a safety barrier. Equipped with preinstalled resistors, the MCP can be used for ESSER Fire Alarm Systems without additional preparation.

Fully addressable large intrinsically safe IQ8MCP, consisting of electronic module and detector housing, for use in the esserbus and powered loop with soft address coding, alarm latch, and alarm indicator. The detector operates like a conventional MCP without the bus connection. IQ8MCP without loop isolator, especially for use in ex-areas. Operation with individual addressing at ex-barrier 804744. Suitable due to the high IP protection up to IP 55 for use in damp rooms.
Fully addressable large intrinsically safe IQ8MCP, consisting of electronic module and detector housing, for use in the esserbus and powered loop with soft address coding, alarm latch, and alarm indicator. The detector operates like a conventional MCP without the bus connection. IQ8MCP without loop isolator, especially for use in ex-areas. Operation with individual addressing at ex-barrier 804744. Suitable due to the high IP protection up to IP 55 for use in damp rooms.
Rated voltage
0.5 - 30 V
Rated current
In < 0.1A / Ik < 4.5A
Connection terminals
0.08-2.5 mm²
Type of protection
IP66
Ex protection
II2G Ex emb IIC T6 Gb; II2D Ex tb IIIC T80°C Db
Material
PC-plastic
Dimensions
W: 135 mm H: 135 mm D: 61 mm
Weight
0.5 kg
Operating temperature
-25 … + 60 °C
Storage temperature
-35 … + 60 °C
Type approval
G206113
EX type approval
BVS 09 ATEX E 016 X