Large IQ8MCP Ex (i), red with glass pane

804924.EX

Approval: G 214114


Fully addressable large intrinsically safe IQ8MCP, consisting of electronic module and detector housing, for use in the esserbus and powered loop with soft address coding, alarm latch, and alarm indicator. The detector operates like a conventional MCP without the bus connection. IQ8MCP without loop isolator, especially for use in ex-areas. Operation with individual addressing at ex-barrier 804744. Suitable due to the high IP protection up to IP 55 for use in damp rooms.

Fully addressable large intrinsically safe IQ8MCP, consisting of electronic module and detector housing, for use in the esserbus and powered loop with soft address coding, alarm latch, and alarm indicator. The detector operates like a conventional MCP without the bus connection. IQ8MCP without loop isolator, especially for use in ex-areas. Operation with individual addressing at ex-barrier 804744. Suitable due to the high IP protection up to IP 55 for use in damp rooms.
Fully addressable large intrinsically safe IQ8MCP, consisting of electronic module and detector housing, for use in the esserbus and powered loop with soft address coding, alarm latch, and alarm indicator. The detector operates like a conventional MCP without the bus connection. IQ8MCP without loop isolator, especially for use in ex-areas. Operation with individual addressing at ex-barrier 804744. Suitable due to the high IP protection up to IP 55 for use in damp rooms.
  • High IP protection up to IP55
  • Plug-in terminals
  • Standard keys with double function: Open, reset
  • Service key with triple function: Test, open, reset
  • "Out of Order" marking an inoperative detector by turning the enclosed operating front foil

Additional Information:
For detailed information on installation and operation, see documentation part no. 798920. For operation with standard groups ex-barrier item no. 764744 must be used in zone 1 and zone 2!

Scope of Delivery:
1 x glass pane 704960
1 x key 769910
1 x Manual call point housing, red
1 x IP 55 shrink sleeve

Operating voltage
8 ... 42 V DC
Quiescent current @ 19 V DC
approx. 45 μA
Alarm display
LED, red
Operation indicator
LED, green
Application temperature -20 °C ... 70 °C
Ambient temperature (Ta)
-20 °C ... 70 °C
Storage temperature
-30 °C ... 75 °C
Max. Output current (Io)
10 mA
Max. Input Voltage (Ui)
21 V DC
Max. Input current (Ii)
252 mA
Explosion protection
Ex ib IIC T4 Gb
Connection terminal
max. 1,5 mm² (AWG 30-14)
Type of protection
IP 44, IP 55 with shrink sleeve
Housing
PC ASA plastic
Air humidity
< 95 %
Color
red, similar to RAL 3020
Weight
approx. 236 g (in housing)
Detector specification
EN 54-11 : 2001 + A1:2005, Typ B
Dimensions