Small Conventional MCP Ex (i) IP 66/67, red with glass pane

804960.EX

Approval: G 214115

The small compact version has detector housing, surface mount housing, transparent cover, and alarm indicator. For connection to a conventional zone for use in ex-areas. Suitable for use in damp rooms thanks to the high IP 66/67 IP protection. Surface mounting housing is provided with break-out cable entries for M20 cable glands (optional) for easy installation.

  • High IP protection class IP66 & IP67
  • Triple key function (test, open, reset)
  • Plug-in terminals
  • Out of Order” indication of an inoperative alarm by
    flipping over the glass pane

Additional Information:
The small compact version has detector housing, surface mount housing, transparent cover, and alarm indicator. For connection to a conventional zone for use in ex-areas. Suitable for use in damp rooms thanks to the high IP 66/67 IP protection. Surface mounting housing is provided with break-out cable entries for M20 cable glands (optional) for easy installation.

Scope of Delivery:
1 x glass pane 704960
1 x key 704966
1 x surface mounting housing
1 x transparent cover

DATA ACCORDING TO ATEX
Max. Input Voltage (Ui)
21 V DC
Max. Input current (Ui)
252 mA
Ambient temperature (Ta)
-20 °C ... 70 °C
EC-type examination certificate
TÜV 14 ATEX 150860
Ex-category
II 2G (with Ex barrier Part-No. 764744 / 804744)
Explosion protection
Ex ib IIC T4 Gb
Specification
EN 60079-0:2012 + A11:2013 / -11:2012
COMMON TECHNICAL DATA
Operating voltage
8 ... 30 V DC
Alarm current @ 9 V DC
typ. 9 mA
Alarm display
red LED and yellow actuation indicator
Connection terminal
max. 1,5 mm² (AWG 30-14)
Application temperature -20 °C ... 70 °C
Storage temperature -20 °C ... 70 °C
Air humidity < 95 % (non condensing)
Type of protection P66, IP67
Material PC ASA plastic
Weight
approx. 255 g
Color red, similar to RAL 3020
Detector specification EN 54-11 : 2001 + A1:2005, Typ A
Dimensions W: 88 mm H: 88 mm D: 63 mm (w. surface mount h.)
Declaration of Performance
DoP-21415141219