esserbus transponder for special detectors

808623.40

For connection of special detectors and associated reset functions with evaluation of pre-alarm, fault and alarm. The transponder module can be adapted to the different reset behaviour of the connected special detectors. The inputs and outputs of the transponder can be linked together in such a way that switching on or resetting a signal input leads to short-term activation of the reset input of the special detector. In order, to support various special detectors, the inputs of the transponder can be programmed with a suppression time of up to 255 seconds at reset.

The transponder can only be operated via FlexES Control with the above mentioned features. With IQ8Control panels, the loop device behaves like an Alarm transponder. Minimum requirements: Tools 8000 ≥ V1.25R000 FlexES Control ≥ V4.07R000 (Container V1.06)

  • 4 detector group inputs for conventional connection of special fire detectors
  • Line monitoring acc. to EN 54-13 possible
  • Integrated loop isolator
  • 2 programmable relay outputs for reset of the special detector with flexible reset times
Operating voltage 10 ... 30 V DC
Contact load relay
30 V DC / 1 A
Quiescent current @ 12 V DC
approx. 12 mA
Current consumption
max. 120 mA @ 12 V DC
Ambient temperature
-10 °C ... 50 °C
Type of protection
IP 40 (in housing)
Air humidity < 95 % (non-condensing)
Weight
approx. 28 g
Dimensions
W: 82 mm H: 72 mm D: 20 mm
Declaration of Performance
DoP-21057130701
  • 781137 DC/DC converter output voltage 24 V DC for the standard-compliant monitoring of the power supply
  • 808624 EOL-O terminating device for the standard-compliant monitoring of the power supply