Approval: EN 54-17
Loop Isolator Module to install a short-circuit and open-circuit tolerant 100 V loudspeaker loop wiring system in VARIODYN D1 loop technology. The modules monitor the current on the loudspeaker ring and disconnect in case of over-current, e.g. in the case of short-circuit, the defective part of the ring from the rest. Loop failures are displayed on DOM and VCM. Each module has a total of three two-pole terminals to connect the loop wiring system and the speakers. Wires can be connected with a section of up to 2.5 mm² to the terminals. Furthermore, a LED of its operating condition is on each module. The Loop Isolator module is housed in a stable, compact IP 66 housing with more of wiring space and is can be use in projects with difficult environmental condition, e.g. industrial use.