ESS-RP1r-Plus

ESS-RP1r-Plus

The ESS-RP1r+ extinguishing control panel has been designed to efficiently manage the automatic release sequence of any extinguishing system of gas or CO2 (according EN12094:1/2003 requirements).
• Compact extinguishing control panel with 32 bits microprocessor.
• Easy configuration from the keyboard
• 3 conventional zones: 2 for detectors and a third one which can be configured for detectors or call points.
• Inputs for abort and gas release call points and hold pushbutton.
• Release delay which can be configured from 0 to 60 sec. and verification time (before activating the sounders) from 0 to 10 min.
• Delays can be disabled from the keyboard (optional).
• Input circuits for flow and low pressure and open door monitoring.
• Two release circuits. The second one can be used independently for preactivation.
• Countdown timer display which indicates the seconds left for release.
• 44 status leds to quickly identify events.
• 7 relays for status indication and operating mode.
• Operating mode: Automatic, Manual and Disabled.
• Digital input for remote action such as: system reset, evacuation, silence or delay on/off.
• Plug-in terminals for all connections.
• Software for status visualization from the PC with remote connection option.
• Certified according to EN54-2/4:A2/2006 and EN12094/1:2003.
Power supply
110/230 Vac; 50/60 Hz.
Standby current
125 mA max.
Total max. current
2.4 A
Batteries
2 x 7A/h
Battery load current
300 mA max.
Battery fuse
F4AL 250 V (4 A)
2 monitored sounder outputs
2 x 250 mA
2 aux. power supply outputs
2 x 250 mA
(resettable and non-resettable)
2 release circuits
1 A max. each circuit
Operating temperature
-5 °C to +40 °C
Operating humidity
95% max. RH
Panel sealing: IP30
Dimensions
W: 381 mm H: 353 mm D: 123 mm
Weight (without/with batteries)
4 Kg / 9.3 Kg
Plug-in Terminals
2,5 mm2 max.
Housing Colour
RAL 7021
Material
ABS V0
  • VSN-232 RS-232 communication module
  • VSN-4REL 4-relay module
  • TFT-SUPRA TFT 4.3" EXTING. RP1r-2Plus/Supra
  • RP1R-RPT REPEATER PANEL FOR EXTING. RP1R
  • VSN-485 RS485 card for RP1R-RPT
  • TG-BASE Dongle with TG w/o license
  • TGP-C GRAPHIC SOFT License for conventional panels RP1r, VSN-2Plus