2-loop analogue addressable gas control panel

AM-8200G

Gas detection control panel, CPR certified in compliance with EN54-2 and EN54-4, with distributed multiprocessor intelligence, set up for the installation of 2 loops expandable up to 4 loops.
The entire system features the “CLIP” communication protocol for complete compatibility with older generation devices. The “CLIP” protocol will support up to 99 detectors and 99 input/output modules for each loop, so it can manage and supervise a maximum of 396 detectors and 396 modules.
Up to 32 remote LCD displays with color touchscreen, model AM-LCDG, can be connected directly to the main board of the control unit via an opto-isolated two-wire RS485 serial bus.
Possibility to print events via an interface to be installed on the control units or to download them onto a USB stick by connecting to the port on the main board of the control unit.

  • 3 password levels (Operator - Maintenance - Configuration).
  • 4 total access levels in compliance with EN54 standards.
  • Programmable texts: 32-character device description; 32-character zone description.
  • 400 physical zones and 400 logical groups for the stand alone control unit.
  • CBE control equations for activations with logical operators (AND, OR, DEL, etc.).
  • Event history archive with the last 10.000 events in non-volatile memory.
  • Real time clock.
  • Self-programming of the line with automatic recognition of the type of connected devices.
  • Automatic recognition of devices with the same address.
  • Decision algorithms for alarm and fault criteria.
  • Programmable alarm and Pre-Alarms thresholds for sensors.
  • Programming of predefined software functions for different devices in the field.
  • Walk-Test function for zones.
  • Siren functionality with programming of different tones
  • Synchronization of sirens and flashing lights
Operating voltage
100-240VAC +/- 15%, 50-60Hz
Battery Charger
27.5 VDC (with temperature compensation)
Charging current
1 A for batteries up to 18Ah
Display
800 x 480 pixels and 256 color touchscreen
Number of loops
2 expandable to 4 with LIB-8200G
Number of zones
400
Number of groups
400
Max. devices per loop
99 detectors and 99 modules
Outputs for alarm devices
1 output 30Vdc 1A
External user outputs
28VDC 1.5A
Alarm relay output
30VDC 2A changeover contact
Fault relay output
changeover contact 30VDC 2A
User 1 and 2 outputs
changeover contact 30VDC 2A
Serial outputs
1 x RS485 standard / 1 x RS-232/RS-485 configurable
Dimensions (H x W x D)
369.8 x 445.7 x 111 mm
Degree of protection IP 30
Operating temperature -5 °C to +40 °C
Storage temperature -10 °C to +50 °C
Weight 6 Kg
  • LIB-8200G Additional board for 2-loops
  • AM-LCDG Gas Remote Repeater panel display on RS485
  • E-SIB-X Enablement key for communication protocols
  • AM-82N-TOP Metal frame for fixed installation of cables on the wall